Model MAXTOP
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
- Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.4 Amps.
FILTERS
- Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
- Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied
with the unit.
DEFROST
- Recirculating damper defrost system.
DEHUMIDISTAT
- Adjustable Internal Dehumidistat.
CASE
- Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS
- ControlAir 15
WEIGHT 87 lbs. (39.5 kg) SHIPPING WEIGHT 89 lbs. (40.5 kg)
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P cfm L/s
@ 0.1” (25 Pa) 196 (93)
@ 0.2” (50 Pa) 188 (89)
@ 0.3” (75 Pa) 178 (84)
@ 0.4” (100 Pa) 165 (78)
@ 0.5” (125 Pa) 149 (71)
Maximum Temperature Recovery 80%
Sensible Effectiveness
@ 117 cfm (55 L/s )
(CSA C439M)
72%
Sensible Efficiency
@ 117 cfm (55 L/s) 32
O
F (0°C) 64%
Sensible Efficiency
@ 67 cfm (31 L/s) -13
O
F (-25°C)
70%
VAC @ 60HZ 120
WATTS / Low speed 74
WATTS / High speed 164
Amp rating 1.4
TOP VIEW
SIDE VIEW
25 1/2 "
(648 mm)
26 1/2"
(673 mm)
22 1/2"
(572 mm)
FRONT VIEW
ALL DUCT CONNECTIONS
ARE 6" (150 mm)
18"
(457 mm)
7 1/2"
(191 mm)
SUPPLY OF
FRESH AIR
FRESH AIR 
SUPPLY
TO BUILDING
STALE AIR
RETURN FROM 
BUILDING
STALE AIR
EXHAUST
DRAIN
CONNECTION
CONTROLS
*Service Clearance
25" (635 mm)
¤
DIMENSIONS MAXTOP
inches (mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control
(PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad
99-163 Duct Heater
w/ Electronic SCR Thermostat, 1 Kw,
6” (150mm)
99-164 Duct Heater
w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.
TI-100-NE
0103
DATE: __________________________
PROJECT: __________________________________________
MECHANICAL CONTRACTOR: _____________________________
511 McCormick Blvd.
London, Ontario
N5W 4C8
Ph: (519) 457-1904
Fx: (519) 457-1676
Website: www.lifebreath.com
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 31 32

Comments to this Manuals

No comments