Page view 4
5
Removably
Heat Recovery
Core
Drain Pan
Drain spout
FRONT TOP
knockout for
side mounting of
EXHAUST return port
6" round collar
converted to oval
minimum
18 inches (459 mm)
required for
service access
Threaded
inserts (4)
at corners
SUPPLY
Fresh air
from outside
5" round collar
SUPPLY
Fresh air
to building
6" round
(conv. to oval)
collar
EXHAUST
Stale Air
to outside
5" round collar
EXHAUST
Return air
from building
Choice of port location
Knockouts on top and
side of unit (use 1 only)
6" round (conv. to oval)
collar supplied
18.5"
(470 mm)
18.5"
(470 mm)
16"
(406 mm)
SIDE
Hanging
straps (4)
24.5"
(622 mm)
Model
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
5 speed fan operation. 120 VAC, .8 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of the cabinet designed to accept PVC rein-
forced polyester straps that are supplied with the unit.
DEFROST
Recirculating defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis-
tance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode,
Recirculation mode, (each mode has 5 speeds). Control pad can be removed
from HRV and remotely mounted.
WEIGHT 52 lbs. (23.6 kg) SHIPPING WEIGHT 56 lbs. (25.4
kg)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat and
Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150 mm)
99-185 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm)
mesh screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery
core and a 5 year replacement parts warranty.
TI-113-NE
1203
95MAX FANCURVE
100
75
50
25
0.1 0.2 0.3 0.4 0.5
Air Flow (cfm)
Static Pressure (inH
2
0)
4
3
2
1
5
HIGH SPEED
MEDIUM HIGH SPEED
MEDIUM SPEED
MEDIUM LOW SPEED
LOW SPEED
4
5
3
2
1
*
*
Manufacturers Data
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P cfm L/s
@ 0.1” (25 Pa) 89 (42)
@ 0.2” (50 Pa) 78 (37)
@ 0.3” (75 Pa) 64 (30)
@ 0.4” (100 Pa) 36 (17)
Maximum Temperature Recovery 74%
Sensible Effectiveness
@ 64 cfm (30 L/s)
(CSA C439M)
74%
Sensible Efficiency
@ 64 cfm (30 L/s) 32˚F (0˚C) 64%
Sensible Efficiency
@ 64 cfm (30 L/s) -13˚F (-25˚C) 58%
VAC @ 60HZ 120
WATTS / Low speed 35
WATTS / High speed 136
Amp rating 0.8
DIMENSIONS 95MAX inches (mm)
All units conform to
CSA and UL standards.
511 McCormick Blvd. 270 Regency Ridge,